GAS-POWDER FIRE EXTINGUISHING MODULE MGPP-11.5-СО2-3.1-RHh-АВСЕ-U2
 
The module provides total flooding extinguishing of fire classes A, B, C and energized electrical equipment in the enclosures of the volume of: V = 60 m3 for Class B fires, V = 90 m3 for Class A fires.
The module is not designed to extinguish the ignition of substances, the combustion of which can occur without access of air, as well as the extinguishing of metals, alloys and organometallic compounds.

 

 

 

ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ

Protected Volume:   
Class А 90 m3
Class В 60 m3
Fire classes according to GOST 27331-87 А, В, С, Е
Extinguishing Agent                                              Gas-Powder
Operation temperature range, 0C -50 С+50 С
Full module weight, max, kg 36,5
Weight of fire-extinguishing powder "Phoenix ABCE-70", kg 7,6
CO2 weight, kg 3,1
Jet length, m 5-6
DC parameters, 
required for module actuation
0.5 A, 6–24 V at duration of 0,02 s
Circuit control safe current, A
0,05 A - during 5 min,
0,005 A – with no time limit
Module response rate max 1s
Duration of discharge max 15 s
Piping options up to 12 m with 3 bends at 900
Overall dimensions, mm 310 х 210 х 750
Service lifetime, min, years 20
   
   