Depending on the characteristics and conditions of the operation, the fire protection system Designer applies the "BiZone" module to the task.
Protected Volume: | |
Class А | 90 m3 |
Class В | 60 m3 |
Explosion proof mark | 1ЕхdsIIBT4 Х |
Fire classes according to GOST 27331-87 | А, В, С, Е |
Extinguishing Agent | Gas-Powder |
Operation temperature range, 0C | -50 С+50 С |
Full module weight, max, kg | 36,5 |
Weight of fire-extinguishing powder "Phoenix ABCE-70", kg | 7,6 |
CO2 weight, kg | 3,1 |
Jet length, m | 5-6 |
DC parameters,
required for module actuation
|
0.5 A, 6–24 V at duration of 0,02 s |
Circuit control safe current, A |
0,05 A - during 5 min,
0,005 A – with no time limit
|
Module response rate | max 1s |
Duration of discharge | max 15 s |
Piping options | up to 12 m with 3 bends at 900 |
Overall dimensions, mm | 310 х 210 х 750 |
Service lifetime, min, years | 20 |