Equipment

>

Depending on the characteristics and conditions of the operation, the fire protection system Designer applies the "BiZone" module to the task.

To request fire protection for your object or to consult with our design engineers, please complete the form below:

Categories

POWDER FIRE EXTINGUISHING MODULE MPP(N)-100-KD-1-BSG-U2
 
The module provides total flooding extinguishing of fire classes A, B, C and energized electrical equipment in the enclosures of the volume of: V = 600 m3 for Class B fires, V = 900 m3 for Class A fires.
The module provides extinguishing class A and B fires over an area of 100 m2.

The module is used in hazardous areas of Class1. Explosion protection marking - 1ExdsIIСT4X.

The module is not designed to extinguish the ignition of substances, the combustion of which can occur without access of air, as well as the extinguishing of metals, alloys and organometallic compounds.

ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ

Protected Volume: 
   
Class A  900 m3
Class В 600 m3
Protected Area 100 m2
Explosion proof mark 1ЕхdsIICT4 Х
Fire classes according to GOST 27331-87 А, В, С, Е
Extinguishing Agent Gas-Powder
Operation temperature range, 0C -50 С+50 С
Full module weight, max, kg  365
Weight of fire-extinguishing powder "Phoenix ABCE-70", kg 80
CO2 weight, kg 30
Jet length, m   18-20

DC parameters,  

required for module actuation 0,5 A6–24VAt duration of 0,02s

2х0.5 A, 6–24 V At, duration of 0,02 s 
Circuit control safe current, A   0,05 A - during 5,
0,005 A – with no time limit
Module response rate max 1 s 
Duration of discharge max 10 s
Piping options                                                                                            up to 100 m with 6 bends at 900   
Overall dimensions, mm 630 х 670 х 1740
Service lifetime, min, years  20

Find us on the map

Contacts

22/1 Zheleznodorozhnaya Street, Sergiev Posad,
Moscow Region, Russia, 141313
e-mail: kalancha@kalancha.ru
e-mail: sales@kalancha.ru

+7 (495) 781 92 48